Frequencies Dominations for Different Rating of Distribution Transformer under Transients

International Journal of Engineering Works 7 (04):211-216 (2020)
  Copy   BIBTEX

Abstract

Power transients faults on high voltage lines are prominently due to high frequency transients. These transients affect the predicted life and efficiency of equipment. The Fast Fourier Transform (FFT) is helpful in analysing the effect of high frequencies and Frequency Response Analysis (FRA) provide support in diagnosis and detection of deformation in a transformers. The major aim of this study is to analyse the incorporation of frequencies based on resonating core of a particular transformer. Using transfer function method an impedance change in transformer has been observed when equipment is subjected to high voltage transients. The effect of change in impedance is that it degrade the life of a core with respect to time. In this paper, research that has been done already on Transformers of different ratings i.e. 100, 50 and 30 kVA are studied and then an experiment is performed on 50-kVA transformer. It was concluded that the core of a transformer having rating equal or less than 50 kVA practically shows single resonance behavior while above 50 kVA for instance 100-kVA transformer core resonates twice. In actual, result defines the core deviating frequency with respect to the rating of a transformer.

Analytics

Added to PP
2020-04-13

Downloads
322 (#69,452)

6 months
85 (#65,178)

Historical graph of downloads since first upload
This graph includes both downloads from PhilArchive and clicks on external links on PhilPapers.
How can I increase my downloads?